Functional Features
Sound emission can be manually adjusted on the sounder itself. At the moment of activation, groups of sounders can be synchronized. Each sounder is provided with integrated isolator circuit, that automatically takes action in case of need. Addresses can be programmed by means of the programmer or with the addressing function of Teledata smoke detection panels.
Technical Features
• Red plastic enclosure
• UNI11744 compliant
• Provided with integrated isolator circuit
• Power supply: 18 ~ 27V
• Average power consumption: 260 μA
• Alarm consumption : 26mA
• Sounder output: 97 dB
• Initiation tripping time: 2 sec
• IP degree: IP65
• Max. Cable cross section 2.5 mm2
• Operating temperature: –10°C /+55°C
• Max. humidity.: 85% non condensing
• Dimensions: diameter 100mm
• Weight: 305g